Sign In | Join Free | My infospaceinc.com
China Ningbo Tianan (Group) Co.,Ltd. logo
Ningbo Tianan (Group) Co.,Ltd.
Ningbo Tianan (Group) Co.,Ltd
Verified Supplier

9 Years

Home > Compact Transformer Substation >

132KV 16000KVA Explosion Proof Prefabricated Distribution Transformer Substation Compact Transformer Substation

Ningbo Tianan (Group) Co.,Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now

132KV 16000KVA Explosion Proof Prefabricated Distribution Transformer Substation Compact Transformer Substation

Brand Name : Tianan Electric

Model Number : CZBT1-132

Certification : IEC

Place of Origin : CHINA

MOQ : 1 unit

Price : Pending

Payment Terms : L/C,D/A,D/P,T/T,Western Union,MoneyGram

Supply Ability : 10000 units/year

Delivery Time : 45 days

Packaging Details : Wooden Carton

Frequency : 50Hz

Special Conditions : Depends on The Customer

System Voltage : 132KV 145Kv

Capacity : 16000KVA

Sound level : ≤65 dB

Protection accuracy : 5P20

Contact Now

132kV Prefabricated Distribution Transformer Substation - Explosion Proof
Vehicle-Mounted Mobile Substation

China's first vehicle-mounted movable substation, delivered to Iraq in December 2008. This 132kV voltage class, 16,000KVA capacity product was completely researched, developed, designed, and manufactured independently.

Modular Design Structure
  • Divided into HV part, main transformer, and LV switchgear room
  • HV switch utilizes ZF10-145(L) as main switch, mounted on semi-trailer
  • LV side includes switchgear, control power, DC panel, and control protection device
Service Conditions
Ambient Conditions
  • Altitude ≤ 1000m
  • Ambient temperature range: -25℃ to +40℃
  • Wind speed (outdoor) ≤ 35m/s
  • Relative humidity ≤ 90% at +25℃
  • Installation location must be free from fire, explosion, chemical corrosion, and excessive vibration
Movement Conditions
  • Maximum speed ≤ 30km/h on flat road surfaces
  • Maximum speed ≤ 10km/h on uneven road surfaces
Note: If the above conditions cannot satisfy requirements, customers can consult with the manufacturer for resolution.
Technical Specifications
General Specifications
ItemUnitParameter
System voltagekV132
Rated voltagekV145
Rated frequencyHz50
Rated currentA2000, 1600
Rated 1min power frequency withstand voltagekV275
Rated lightning impulse withstand voltagekV650
Rated short time withstand currentkA25, 31.5, 40
Rated short time withstand times3
Rated peak withstand currentkA63, 80, 100
Circuit Breaker Specifications
ItemUnitParameter
System voltagekV132
Rated voltagekV145
Rated frequencyHz50
Rated currentA2000
Rated 1min power frequency withstand voltagekV275
Rated lightning impulse withstand voltagekV650
Rated short time withstand current / timekA/s40/4
Rated peak withstand currentkA100
Rated short circuit breaking currentkA40
Rated short circuit making currentkA100
DC component%40
Rated operation sequenceO _0.3s_ CO _180s_ CO
Opening timems35±5
Closing timems105±15
Breaking timems≤60
Non-simultaneity between poles - Closingms≤5
Non-simultaneity between poles - Openingms≤3
Fracture no. of each pole1
Mechanical enduranceTimes≥6000
Full capacity continuous breaking timesTimes≥20
SF6 gas pressure (20℃) - Rated valueMPa0.60
SF6 gas pressure (20℃) - Alarm valueMPa0.55
SF6 gas pressure (20℃) - Locking valueMPa0.50
SF6 gas moisture content - Acceptance valuePPm≤150
SF6 gas moisture content - Operation allowable valuePPm≤300
SF6 yearly gas leakage rate%≤0.5
Total weight of each circuit breakerkg2000
Current Transformer Parameters
Current RatioRated Output Capacity VAMeasure Accuracy LevelProtection Accuracy Level
150/5200.55P20
300/5200.55P20
500/5300.55P20
750/530, 400.55P20
1000/540, 500.55P20
1500/5500.55P20
2000/5500.55P20
Note: Straight-through type bushing current transformer is attached in the circuit breaker.
Lightning Arrester Parameters
ItemUnitParameter
System voltagekV132
Rated voltagekV150
Rated frequencyHz50
Nominal discharge currentkA10
DC 1mA reference voltagekV≥245
Residual voltage under lightning impulse current (peak)kV≤435
Residual voltage under operation impulse current (peak)kV≤370
Residual voltage under steep wave impulse current (peak)kV≤490
Neutral Point Lightning Arrester Parameters
ItemUnitParameter
System voltagekV132
Rated voltagekV90
Rated frequencyHz50
Nominal discharge currentkA1.5
DC 1mA reference voltagekV≥140
Residual voltage under lightning impulse current (peak)kV≤260
Residual voltage under operation impulse current (peak)kV≤240
Residual voltage under steep wave impulse current (peak)kV/
Low Voltage Side Switch Equipment Parameters
ItemUnitParameter
System voltagekV11.5
Rated voltagekV12
Rated frequencyHz50
Rated currentA2000, 1600, 1250
Rated 1min power frequency withstand voltagekV42/48
Rated lightning impulse withstand voltagekV75/85
Rated short time withstand currentkA40, 31.5, 25
Rated short time withstand times4
Rated peak withstand currentkA100, 80, 63
Rated short circuit breaking currentkA40, 31.5, 25
Rated short circuit making currentkA100, 80, 63
Rated operation sequenceO _0.3s_ CO _180s_ CO
Mechanical enduranceTimes≥10000
132KV 16000KVA Explosion Proof Prefabricated Distribution Transformer Substation Compact Transformer Substation

Product Tags:

Explosion Proof Distribution Transformer Substation

      

Prefabricated Distribution Transformer Substation

      

Prefabricated power distribution transformer

      
Quality 132KV 16000KVA Explosion Proof Prefabricated Distribution Transformer Substation Compact Transformer Substation for sale

132KV 16000KVA Explosion Proof Prefabricated Distribution Transformer Substation Compact Transformer Substation Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Ningbo Tianan (Group) Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)